Eurocode 1 Thermal Actions for External Members

Introduction

This method 1 allows the determination of:

  • the maximum temperatures of a compartment fire;

  • the size and temperatures of the flame from openings;

  • radiation and convection parameters.

Important

  1. This method considers steady-state conditions for the various parameters.

  2. The method is valid only for fire loads \(q_{f,d}\) higher than 200 \(MJ/m^2\).

  3. All parts of an external wall that do not have the fire resistance (REI) required for the stability of the building should be classified as window areas.

  4. The size of the fire compartment should not exceed 70 m in length, 18 m in width and 5 m in height.

  5. The flame temperature should be taken as uniform across the width and the thickness of the flame.

  6. Clause B.3 considers wind effects which is currently NOT included in this document.

Fire Compartment Figure

Fig. 5 Illustration of a fire compartment with vertical window opening and optional core

Where
\(W_1\) [\(m\)], is the wall with greatest window opening area.
\(W_2\) [\(m\)], is the wall with lesser window opening area as compared to \(W_2\).
\(A_{v1}\) [\(m^2\)], is the total window opening area on \(W_1\). \(A_{v1}=A_v\) if window only exist on \(W_1\).
\(A_{v}\) [\(m^2\)], is the total window opening area on all walls.
\(W_c\) [\(m\)], is the width of core. Set to 0 if no core is present.
\(L_c\) [\(m\)], is the depth of core. Set to 0 if no core is present.
\(w_t\) [\(m\)], is the sum of window widths (\(w_t=\sum_{i=1}^{\text{tot. win.}}{w_i}\)).
\(h_{eq}\) [\(m\)], is weighted average height of all windows.
\(S_w\) [\(m\)], is the separation between windows.
\(\mathrm{B}_w\) [\(1\)], \(\mathrm{B}_w=True\) means there is wall above the window, otherwise \(\mathrm{B}_w=False\).

Opening factor

Opening factor of the fire compartment is given by Equation (1) (Clause 1.6(1)).

(1)\[O=\frac{A_v\sqrt{h_{eq}}}{A_t}\]
where
\(O\) [\(m^{0.5}\)], is the opening factor of the fire compartment.
\(A_v\) [\(m^2\)], is the total area of vertical openings on all walls.
\(A_t\) [\(m^2\)], is the total area of enclosure (walls, ceiling and floor, including openings).

Compartment \(D/W\)

The compartment and opening arrangement is partly described by the \(D/W\) is given by Equation (2) (Clause B.2, BS EN 1991-1-2:2002).

(2)\[D/W=\frac{W_2-L_c}{W_1-W_c}\frac{A_{v1}}{A_v}\]

No Forced Draught (NFD)

Heat release rate (NFD)

The rate of burning or the rate of heat release is given by Equation (3) (Clause B.4.1(1), Equation B.4).

(3)\[\begin{split}Q=\min\begin{Bmatrix} \frac{A_f\cdot q_{f,d}}{\tau_F}\\ 3.15\left(1-e^\frac{-0.036}{O}\right)A_v\sqrt{\frac{h_{eq}}{D/W}} \end{Bmatrix}\end{split}\]
Where
\(Q\) [\(MW\)], is the rate of heat release.
\(A_f\) [\(m^2\)], is the compartment floor area.
\(q_{td}\) [\(MJ/m^2\)], is the design fuel load density.
\(\tau_F\) [\(s\)], is the free burning fire duration (assumed to be 1200 [\(s\)]).
\(O\) [\(?\)], is the opening factor as per Equation (1).

Flame height (NFD)

The flame height is given by Equation (4) (Clause B.4.1(3), Equation B.6).

(4)\[\begin{split}L_L = \max \begin{Bmatrix} 0\\ h_{eq}\left(2.37\left(\frac{Q}{A_v\rho_g\sqrt{h_{eq}g}}\right)^{2/3}-1\right) \end{Bmatrix}\end{split}\]
Where
\(L_L\) [\(m\)], is the flame height.
\(\rho_g\) [\(kg/m^3\)], is the air density.
\(g\) [\(m/s^2\)], is the gravity.

Note

With \(\rho_g=0.45kg/m^3\) and \(g=9.81m/s^2\), Equation (4) may be simplified to \(L_L =\left(1.9\frac{Q}{w_t}\right)^{2/3}-h_{eq}\)

Flame horizontal projection (NFD)

The horizontal projection of the flame is given by Equation (5) (Clause 4.1(6), Equation B.8 to B.11).

(5)\[\begin{split}L_H= \begin{cases} & \text{if }\mathrm{B}_w\text{ and }h_{eq}\le1.25w_t &1/3\cdot h_{eq}\\ & \text{else if }\mathrm{B}_w\text{ and }h_{eq}>1.25w_t\text{ and }S_w>4w_t &0.3h_{eq}\left(\frac{h_{eq}}{w_t}\right)^{0.54}\\ & \text{else if }\mathrm{B}_w &0.454h_{eq}\left(\frac{h_{eq}}{2w_t}\right)^{0.54}\\ & \text{else if }\mathrm{B}_w=False &0.6h_{eq}\left(\frac{L_L}{h_{eq}}\right)^{1/3} \end{cases}\end{split}\]
Where
\(L_H\) [\(m\)], is the horizontal projection of the external flame.

Flame length (NFD)

The flame length along axis is given by Equation (6) (Clause B.4.1(7), Equation B.12 & B.13).

(6)\[\begin{split}L_f= \begin{cases} &\text{if }\mathrm{B}_w\text{ and }h_{eq}\le1.25w_t &L_L+0.5h_{eq}\\ &\text{else }&\sqrt{L_L^2+\left(L_H=h_{eq}/3\right)^2}+0.5h_{eq} \end{cases}\end{split}\]
Where
\(L_f\) [\(m\)], is the flame length along axis.

Flame temperature at the window (NFD)

The flame temperature at the window is given by Equation (7) (Clause B.4.1(8), Equation B.14).

(7)\[T_w=\frac{520}{1-0.4725L_f\cdot w_t/Q}+T_0\]
Where
\(T_w\) [\(K\)], is the flame temperature at the window.
\(T_0\) [\(K\)], is the ambient temperature.

Flame temperature along the axis (NFD)

The flame temperature along the axis is given by Equation (8) (Clause B.4.1(10), Equation B.15).

(8)\[T_z=\left(T_w-T_0\right)\left(1-0.4725\frac{L_x\cdot w_t}{Q}\right)+T_0\]
Where
\(T_z\) [\(K\)], is the flame temperature along the axis at \(L_x\).
\(L_x\) [\(m\)], is the axis length from the window to the point where the calculation is made.

The following parameters are not used to derive the external flame dimension and temperature (e.g. \(L_H\), \(L_L\) and \(T_z\) etc.) but are may be used for other purposes (e.g., to derive external steel temperature).

Compartment temperature (NFD)

The temperature of the fire compartment is given by Equation (9) (Clause B.4.1(2), Equation B.5).

(9)\[T_f=6000\left(1-e^{-0.1/O}\right)O^{-1/2}\left(1-e^{-0.00286\Omega}\right)+T_0\]
Where
\(T_f\) [\(K\)], is the temperature of the fire compartment.

Forced Draught (FD)

Heat release rate (FD)

The rate of burning or the rate of heat release is given by Equation (10) (Clause B.4.2(1), Equation B.18).

(10)\[Q=\frac{A_f\cdot q_{f,d}}{\tau_F}\]
Where
\(Q\) [\(MW\)], is the rate of heat release.
\(\tau_F\) [\(s\)], is the free burning fire duration (assumed to be 1200 [\(s\)]).

Fire compartment temperature (FD)

The temperature of the fire compartment is given by Equation (11) (Clause B.4.2(2), Equation B.19).

(11)\[T_f=1200\left(1-e^{-0.00228\Omega}\right)+T_0\]
Where
\(T_f\) [\(K\)], is the temperature of the fire compartment.

Flame height (FD)

The flame height is given by Equation (12) (Clause B.4.2(3), Equation B.20).

(12)\[L_L=\left(1366\left(\frac{1}{u}\right)^{0.43}\frac{Q}{\sqrt{A_f}}\right)-h_{eq}\]
Where
\(L_L\) [\(m\)], is the flame height.

Flame horizontal projection (FD)

The horizontal projection of flames is given by Equation (13) (Clause B.4.2(4), Equation B.21).

(13)\[L_H=0.605\left(\frac{u^2}{h_{eq}}\right)^{0.22}\left(L_L+h_{eq}\right)\]
Where
\(L_H\) [\(m\)], is the horizontal projection of flame.

Note

With \(u=6m/s\), \(L_H=1.33\left(L_L+h_{eq}\right)/h_{eq}^{0.22}\)

Flame width (FD)

The flame width is given by Equation (14) (Clause B.4.2(5), Equation B.22).

(14)\[w_f=w_t+0.4L_H\]
Where
\(w_f\) [\(m\)], is the flame width.

Flame length (FD)

The flame length along axis is given by Equation (15) (Clause B.4.2(6), Equation B.23).

(15)\[L_f=\sqrt{L_L^2+L_H^2}\]
Where
\(L_f\) [\(m\)], is the flame length along axis.

Flame temperature at the window (FD)

The flame temperature at the window is given by Equation (16) (Clause B.4.2(7), Equation B.24).

(16)\[T_w=\frac{520}{1-0.3325L_f\frac{\sqrt{A_v}}{Q}}+T_0\]
Where
\(T_w\) [\(K\)], is the flame temperature at the window.

Warning

\(L_f\sqrt{A_v}/Q<1\).

Flame temperature along the axis (FD)

The flame temperature along the axis is given by Equation (17) (Clause B.4.2(9), Equation B.25).

(17)\[T_z=\left(1-0.3325\frac{L_x\sqrt{A_v}}{Q}\right)\left(T_w-T_0s\right)+T_0\]
Where
\(T_z\) [\(K\)], is the flame temperature along the axis.
\(L_x\) [\(m\)], is the axis length from the window to the point where the calculation is made.

Miscellaneous

Some parameters that are documented in 1 but they are more relevant to

Flame emissivity

The emissivity of flame is given by Equation (18) (Clause B.4.1(11), Equation B.16).

(18)\[\varepsilon_f=1-e^{-0.3d_f}\]
Where
\(\varepsilon_f\) [\(1\)], is the emissivity of flames.

Convective heat transfer coefficient

The convective heat transfer coefficient is given by Equation (19) (Clause B.4.1(12), Equation B.17).

(19)\[\alpha_c=4.67\left(1/d_{eq}\right)^{0.4}\left(Q/A_v\right)^{0.6}\]
Where
\(\alpha_c\) [\(1\)], is the convective heat transfer coefficient of the flame.

Overall Configuration Factors

Radiative heat transfer from an opening

The overall configuration factor \(\phi_f\), of a member for radiative heat transfer from an opening should be determined from Equation (20) (Clause B5(1), Equation B.28).

(20)\[\phi_f=\frac{\left(C_1\phi_{f,1}+C_2\phi_{f,2}\right)d_1+\left(C_3\phi_{f,3}+C_4\phi_{f,4}\right)d_2}{\left(C_1+C_2\right)d_1+\left(C_3+C_4\right)d_2}\]
Where
\(\phi_{f,i}\) [\(1\)], is the configuration factor of member face i for that opening.
\(d_i\) [\(1\)], is the cross-sectional dimension of member face \(i\).
\(C_i\) [\(1\)], is the protection coefficient of member face \(i\) as follows:
for a protected face: \(C_i=0\).
for an unprotected face: \(C_i=1\).

The configuration factor \(\phi_{f,i}\), for a member face from which the opening is not visible should be taken as zero.

Radiative heat transfer from a flame

The overall configuration factor \(\phi_z\) of a member for radiative heat transfer from a flame should be determined from Equation (21) (Clause B5(3), Equation B.29).

(21)\[\phi_z=\frac{\left(C_1\phi_{z,1}+C_2\phi_{z,2}\right)d_1+\left(C_3\phi_{z,3}+C_4\phi_{z,4}\right)d_2}{\left(C_1+C_2\right)d_1+\left(C_3+C_4\right)d_2}\]
Where
\(\phi_{z,i}\) [\(1\)], is the configuration factor of member face i for that flame.

The configuration factors \(\phi_{z,i}\) of individual member faces for radiative heat transfer from flames may be based on equivalent rectangular flame dimensions. The dimensions and locations of equivalent rectangles representing the front and sides of a flame for this purpose should be determined as given in annex G. For all other purposes, the flame dimensions given in B.4 of this annex should be used.

Reference

1(1,2)

BSI, BS ISO 834-1:1999 Fire resistance tests. Elements of building construction. General requirements., BSI, London, Sep. 1991.